Maximum maintain or continuous exposure temperature(power on)
65℃
Maximum intermittent exposure temperature, 1000 hours (power on or off)
85℃
Minimum installation temperature
-40℃
3 BTV-CR/CT
Ambient
Maximum circuit Length (in Meter) per circuit breaker
temperature
120V
240V
at start-up
15A
20A
30A
40A
10℃
101
201
-18℃
61
81
120
162
-29℃
53
72
107
142
47
62
94
125
189
5 BTV-CR/CT
70
82
140
165
43
58
87
116
38
50
76
152
34
44
67
90
134
8 BTV-CR/CT
46
64
91
122
128
30
40
26
35
24
32
96
10 BTV-CR/CT
37
49
55
73
110
66
99
21
29
20
52
78
104
121℃
215℃
5 HXTV
50A
117
146
219
233
98
191
93
181
59
88
174
232
10 HXTV
79
157
56
75
113
151
27
108
143
15 HXTV
23
136
41
102
18
123
20 HXTV
15
84
105
260℃
Maximum Continuous maintain (power on) temperature table
CABLE
208V
230V
277V
480V
5VPL1-CT
230℃
10VPL1-CT
205℃
15VPL1-CT
170℃
20VPL1-CT
150℃
5VPL2-CT
235℃
225℃
10VPL2-CT
220℃
210℃
200℃
15VPL2-CT
190℃
115℃
20VPL2-CT
5VPL4-CT
10VPL4-CT
15VPL4-CT
20VPL4-CT
VPL 5W - MAXIMUM CIRCUIT LENGTHS BASED ON CIRCUIT BREAKER SIZE
260
160
209
226
320
418
451
240
148
197
296
393
235
287
381
225
69
139
186
277
372
VPL 10W - MAXIMUM CIRCUIT LENGTHS BASED ON CIRCUIT BREAKER SIZE
158
213
149
198
299
145
192
290
283
VPL 15W - MAXIMUM CIRCUIT LENGTHS BASED ON CIRCUIT BREAKER SIZE
131
262
10
130
195
259
126
253